Press connector system made of fibre-glass reinforced polyamide. Permitted types of pipe PE 80/100/100-RC. Sealed inside. Support sleeve function integrated into the press connector. Suitable for underground, municipal supply lines.
For connecting the house service connection to unpressurised and pressurised supply lines. Permitted pipe types PE80, PE100 HDPE and PE100 HSCR.
Labeling Manufacturer, Pipe dimension, Batch, Green dot at press end when used for potable water, Traceability-Code for component tracing
Press connector with Smart Connect Feature Inadvertently unpressed connections become visibly leaky when the system is filled. Viega guarantees the detection of unpressed connections in the following pressure ranges: min. water pressure: 0.1 MPa / 100 kPa / 1 bar / 14.5 PSI max. water pressure: 0.65 MPa / 650 kPa / 6.5 bar / 94.3 PSI min. air pressure: 22 hPa / 2.2 kPa / 22 mbar / 0.3 PSI max. air pressure: 0.3 MPa / 300 kPa / 3 bar / 43.5 PSI
Dimensions d25–63, Tapping valves: d63–200
Tools The functional safety of Viega press connector systems depends primarily on the faultless condition of the press tools used. Viega recommends the use of Viega press tools for pressing Viega press connectors. Viega press tools have to be regularly maintained by authorised service partners.
Areas of application Potable water Geothermal energy / cold local heat
Note Use of the system for areas of application and media other than those described must be agreed in consultation with Viega. Detailed information concerning applications, limitations and national codes and standards can be found in the product documentation, either printed or on the Viega website.
Note – Standards and approvals Permitted pipe types for potable water pipelines and potable water tapping valves: PE-X in accordance with DIN 16893, DIN 16892, GW 335-A3. PE 80/100/100-RC in accordance with DIN 8074, DIN 8075, DIN EN 12201, GW 335-A2.
Operating conditions potable water installations operating temperature max. 25 °C / 77 °F operating pressure max. 1.6 MPa / 16 bar / 232 PSI The maximum operating pressure and the maximum temperature depend on the type of pipe used and the specific application and have to be tested in particular cases.
Changes and errors excepted. Latest Z- and installation dimensions as well as further technical information can be found on the Viega website and have to be checked before purchase, planning, construction work and use. Our products are continuously optimized.
This product description contains important information on choice of product and system, mounting, commissioning as well as intended use and, if required, on maintenance measures. This information on products, their features and application techniques is based on currently valid standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW). Some passages in the text may refer to technical regulations in Europe/Germany. These should be considered as recommendations for other countries where no corresponding national requirements exist. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this product description: The information herein is not binding for other countries and regions and should be understood as recommendation.
Our website uses cookies to help you to get the best out of its content, to improve your experience and to collect statistical data. We do not use cookies to create user profiles. Please refer to our Data protection statement for more information